• An ISO 9001:2015, 14001:2015 & 45001:2018 Company

LT PVC Power Cables

slider images
LT PVC Power Cables

LT PVC Power Cable: The Backbone of Low Voltage Power Distribution

Our LT PVC Power Cable is engineered to be the reliable foundation of low voltage power distribution networks. These cables feature a robust PVC (Polyvinyl Chloride) insulation, ensuring dependable electrical performance and durability. Tailored for low-tension applications, our LT PVC Power Cables provide a cost-effective solution for residential, commercial, and industrial power requirements. With efficient energy transmission and resistance to environmental factors, our LT PVC Power Cables deliver a steady and efficient flow of electricity, supporting the diverse needs of low voltage power distribution with unwavering reliability.

  • IS 1554 - 1
  • IEC 60502-1
  • BS 6724
  • BS 6004
  • BS 6346
TABLE 1
SINGLE CORE PVC INSULATED CABLES ACCORDING TO IS 1554 - 1
Conductor cross sectional Area
Insulation Thickness
Diameter of Round wire armour
Outersheath Thickness
Armoured
Unarmoured
Flat strip armoured cable
Round wire armoured cable
Unarmoured cable
Nominal
Nominal
Nominal
Minimum
Minimum
Nominal
sqmm
mm
mm
mm
mm
mm
mm
10
-
1.00
-
-
-
1.80
16
-
1.00
-
-
-
1.80
25
1.50
1.20
1.40
1.24
1.24
1.80
35
1.50
1.20
1.40
1.24
1.24
1.80
50
1.70
1.40
1.40
1.24
1.24
1.80
70
1.70
1.40
1.40
1.24
1.40
1.80
95
1.90
1.60
1.60
1.40
1.40
1.80
120
1.90
1.60
1.60
1.40
1.40
2.00
150
2.10
1.80
1.60
1.40
1.40
2.00
185
2.30
2.00
1.60
1.40
1.40
2.00
240
2.50
2.20
1.60
1.40
1.56
2.00
300
2.70
2.40
1.60
1.56
1.56
2.00
400
3.00
2.60
2.00
1.56
1.56
2.20
500
3.40
3.00
2.00
1.56
1.72
2.20
630
3.90
3.40
2.00
1.72
1.88
2.40
800
3.90
3.40
2
1.88
1.88
2.40
1000
3.90
3.40
2.5
2.04
2.04
2.60
TABLE 2
TWO CORE PVC INSULATED CABLES ACCORDING TO IS 1554 - 1
Conductor cross sectional Area
Insulation Thickness
Innersheath Thickness
Diameter of Round wire armour
Outersheath Thickness
Flat strip armoured cable
Round wire armoured cable
Unarmoured cable
Nominal
Minimum
Nominal
Minimum
Minimum
Nominal
sqmm
mm
mm
mm
mm
mm
mm
1.50
0.80
0.30
1.40
-
1.24
1.80
2.50
0.90
0.30
1.40
-
1.24
1.80
4
1.00
0.30
1.40
-
1.24
1.80
6
1.00
0.30
1.40
-
1.24
1.80
10
1.00
0.30
1.40
-
1.24
1.80
16
1.00
0.30
1.60
1.40
1.40
1.80
25
1.20
0.30
1.60
1.40
1.40
2.00
35
1.20
0.30
1.60
1.40
1.40
2.00
50
1.40
0.30
1.60
1.40
1.56
2.00
70
1.40
0.30
1.60
1.56
1.56
2.00
95
1.60
0.40
2.00
1.56
1.56
2.20
120
1.60
0.40
2.00
1.56
1.72
2.20
150
1.80
0.40
2.00
1.72
1.72
2.40
185
2.00
0.50
2.00
1.88
1.88
2.40
240
2.20
0.50
2.50
2.04
2.04
2.60
300
2.40
0.60
2.50
2.20
2.20
2.80
400
2.60
0.70
3.15
2.36
2.52
3.20
500
3.00
0.70
3.15
2.68
2.84
3.40
630
3.40
0.70
4.00
2.84
3.00
3.80
TABLE 3
THREE CORE PVC INSULATED CABLES ACCORDING TO IS 1554 -1
Conductor cross sectional Area
Insulation Thickness
Innersheath Thickness
Diameter of Round wire armour
Outersheath Thickness
Flat strip armoured cable
Round wire armoured cable
Unarmoured cable
Nominal
Minimum
Nominal
Minimum
Minimum
Nominal
sqmm
mm
mm
mm
mm
mm
mm
1.50
0.80
0.30
1.40
-
1.24
1.80
2.50
0.90
0.30
1.40
-
1.24
1.80
4
1.00
0.30
1.40
-
1.24
1.80
6
1.00
0.30
1.40
-
1.24
1.80
10
1.00
0.30
1.40
-
1.40
1.80
16
1.00
0.30
1.60
1.40
1.40
1.80
25
1.20
0.30
1.60
1.40
1.40
2.00
35
1.20
0.30
1.60
1.40
1.40
2.00
50
1.40
0.30
1.60
1.56
1.56
2.00
70
1.40
0.40
2.00
1.56
1.56
2.20
95
1.60
0.40
2.00
1.56
1.72
2.20
120
1.60
0.40
2.00
1.72
1.72
2.20
150
1.80
0.50
2.00
1.88
1.88
2.40
185
2.00
0.50
2.50
1.88
2.04
2.60
240
2.20
0.60
2.50
2.20
2.20
2.80
300
2.40
0.60
2.50
2.36
2.36
3.00
400
2.60
0.70
3.15
2.52
2.68
3.40
500
3.00
0.70
3.15
2.84
3.00
3.60
630
3.40
0.70
4.00
3.00
3.00
4.00
TABLE 4
THREE CORE WITH REDUCED NEUTRAL CORE PVC INSULATED CABLES ACCORDING TO IS 1554 - 1
Conductor cross sectional Area
Insulation Thickness
Innersheath Thickness
Diameter of Round wire armour
Outersheath Thickness
Flat strip armoured cable
Round wire armoured cable
Unarmoured cable
Nominal
Minimum
Nominal
Minimum
Minimum
Nominal
sqmm
mm
mm
mm
mm
mm
mm
25
1.20
0.30
1.60
1.40
1.40
2.00
35
1.20
0.30
1.60
1.40
1.40
2.00
50
1.40
0.30
1.60
1.56
1.56
2.00
70
1.40
0.40
2.00
1.56
1.56
2.20
95
1.60
0.40
2.00
1.56
1.72
2.20
120
1.60
0.50
2.00
1.72
1.88
2.40
150
1.80
0.50
2.00
1.88
1.88
2.40
185
2.00
0.50
2.50
2.04
2.04
2.60
240
2.20
0.60
2.50
2.20
2.36
3.00
300
2.40
0.60
3.15
2.36
2.52
3.20
400
2.60
0.70
3.15
2.68
2.68
3.40
500
3.00
0.70
4.00
2.84
3.00
3.80
630
3.40
0.70
4.00
3.00
3.00
4.00
TABLE 5
FOUR CORE PVC INSULATED CABLES ACCORDING TO IS 1554 - 1
Conductor cross sectional Area
Insulation Thickness
Innersheath Thickness
Diameter of Round wire armour
Outersheath Thickness
Flat strip armoured cable
Round wire armoured cable
Unarmoured cable
Nominal
Minimum
Nominal
Minimum
Minimum
Nominal
sqmm
mm
mm
mm
mm
mm
mm
1.50
0.80
0.30
1.40
-
1.24
1.80
2.50
0.90
0.30
1.40
-
1.24
1.80
4
1.00
0.30
1.40
-
1.24
1.80
6
1.00
0.30
1.40
-
1.24
1.80
10
1.00
0.30
1.60
1.40
1.40
1.80
16
1.00
0.30
1.60
1.40
1.40
2.00
25
1.20
0.30
1.60
1.40
1.40
2.00
35
1.20
0.30
1.60
1.40
1.56
2.00
50
1.40
0.40
2.00
1.56
1.56
2.20
70
1.40
0.40
2.00
1.56
1.56
2.20
95
1.60
0.40
2.00
1.72
1.72
2.40
120
1.60
0.50
2.00
1.88
1.88
2.40
150
1.80
0.50
2.50
1.88
2.04
2.60
185
2.00
0.60
2.50
2.04
2.20
2.80
240
2.20
0.60
2.50
2.36
2.36
3.00
300
2.40
0.70
3.15
2.52
2.68
3.40
400
2.60
0.70
3.15
2.84
2.84
3.60
500
3.00
0.70
4.00
3.00
3.00
4.00
630
3.40
0.70
4.00
3.00
3.00
4.00

Note:-
1. Changes that improve our product will be done without notice.
2. If there is any discrepancy found above, the applicable standard will prevail.

Company Profile